Model | FDC900KXZE1 | ||
Combination (FDC) | 450KXZE1 + 450KXZE1 | ||
Norminal Horse Power | 32HP | ||
Power Source | Ph/V/Hz | 3 / 380-415 / 50 | |
Starting Current | A | 10 | |
Max. Current | A | 64 | |
Nominal Cooling Capacity | Min~Max | kW | 90.0 |
Nominal Heating Capacity | Min~Max | kW | 100.0 |
Power Consumption | Cooling/Heating | kW | 27.96 / 25.00 |
Dimension (H x W x D) | mm | 2048 x 2700 x 720 | |
Net Weight | kg | 634 | |
Refrigerant Charge | R410A | kg | 11.5 x 2 |
Refrigerant Piping Size | Liquid / Gas | mm(in) | 15.88(5/8”) / 31.75(1 1/4”)[34.92(1 3/8”)] |
Capacity Connection | % | 50-130 | |
Number of Connectable Indoor Units | 78 |